17
For 1½ HP (and Larger)
Control Box
1. Set Ohmmeter at “R x 1”2. Connect the Ohmmeter leads to Terminal
#1 and #3 on each Overload Protector.
3. Reading should be not more than 0.5
Ohms maximum on the scale.
CSCr or mag. Contactor Control box
O
VERL
AD CHECK
OUT