Aquavar SOLO –

Quick Installation Guide

1. mount Aquavar SOlO Drive (in a vertical position);

• Must have 6” minimum clearance on all sides for proper cool-

ing.

2. Wire input Power to SOlO Drive (Single Phase, 230V)

• Review Circuit Breaker Sizing see IMS-SOLOQ-2 or IM229

3. Wire motor Drop Cable to SOlO Drive

(75˚C Copper Wire min.)

• 3AS Models - Use with Three Phase, 230V, ¾ to 5 HP Motors
• 1AS15 Model - Compatible w/Single Phase, 230V Motors

3-Wire - .5 - 2 HP CP / Pentek XE; .5 – 1.5 HP FE & Grundfos

2-Wire - .5 – 1.5 CentriPro, Pentek XE, Franklin Elec. & Grund-

fos 2-Wire – units with R05K or newer software only.

• Review Wire Sizing (Table 4 of IM229)

4. mount transducer and Confirm transducer Cable Wiring

• Transducer cable maximum length = 200 feet
• Connect Pressure Transducer to piping manifold and to ground

5. user interface board Adjustments

• Select proper “Current Limit Setting” (equal to motor SFA)
• 1AS15 Only - Set “Pump Stop Sensitivity” - High is Default
• 3AS_ _ Only - Select maximum frequency setting (60 Hz or

80 Hz);

60 Hz = matching Liquid End HP and Motor HP

80 Hz = “over-speed” application; motor HP > Liquid End HP

• Dry Well Sensitivity - Set on “High” position;

If nuisance tripping occurs, switch to “Low” position

• Low Pressure Cut-Off and Pressure Drop setting adjusted to

application / system requirements.

• Optional use of Secondary Switch Connection, refer to IM229

6. Adjust tank Pressure

• Set approximately 20 PSI below pressure set point
• Adjust as needed to optimize - see IMS-SOLOQ-2 or IM229

7. turn Drive Power On - Adjust Pressure - Purge Air

• Purge air from system and check for leaks
• Factory default is 50 psi - push and hold Increase Pressure

button if higher pressure is desired and also adjust tank pre-
charge.

8. Check motor rotation and Confirm Performance

Refer to Aquavar SOLO Installation Manual, IM229, for complete
details. Check Motor Insulation Resistance on retrofit jobs before
replacing drive.