Checking Voltage at Fused

Disconnect and Magnetic

Starter

1. To check voltage: Use voltmeter on L1, L2

and L3 in sequence. Check should be made

at four locations.

Step 1 Checking incoming power supply.

Step 2 Checking fuses.

Step 3 Checking contact points

Step 4 Checking heaters.
2. When checking voltage, all other major

electrical appliances (that could be in use at

the same time) should be running.

3. If incoming power supply readings are not

within the limits (see chart), call your power

supplier.

NOTE: Phase to phase – full line voltage.

Phase to neutral – ½ full line voltage.
(depending on transformer connection)

!

WARNING!

Power is ON during voltage checking.

Voltage Limits

Name Plate

Measured Volts

Minimum Maximum

208V 3Ø

188

228

230V 3Ø

207

253

460V 3Ø

414

506

575V 3Ø

518

632