Units with 1ø input and 3ø output (motors), Aqu a v ar sol o wire sizing, Service entrance to controller – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual

Page 52: Controller to motor

Advertising
background image

A

QU

A

V

AR SOL

O

WIRE SIZING

50

Service Entrance to Controller

Controller Motor

Input

HP 14 12 10 8 6 4 2

1/0 2/0 3/0 4/0 250 300 350 400 500

½ 366 583 925 1336 2107 3345 5267

8364

¾ 279 445 706 1020 1608 2552 4019

6383 8055

230V

1 226 360 571 824 1300 2064 3250

5161 6513 8201

1½ * 286 455 657 1036 1644 2589

4111 5188 6533 8236 9710

2 * * 331 478 754 1197 1886

2995 3779 4759 5999 7073 8455 9852

3 * * 246 355 561 890 1401

2225 2808 3536 4458 5256 6283 7321 8343

5 * * * 218 343 545 858

1363 1720 2165 2730 3219 3847 4483 5109 6348

Controller to Motor

Controller Motor

Output

HP 14 12 10 8 6

4 2 1/0 2/0 3/0 4/0 250 300

½ 905 1442 2290 3306 5213

8276

¾ 690 1100 1748 2523 3978

6316

9945

230V

1 558 890 1413 2040 3216

5106

8041

1½ 445 709 1126 1625 2562

4068

6406

2 324 516 820 1184 1866

2963

4666

7410

9351

3 241 384 609 880 1387

2202

3467

5506

6949

8750

5

*

235 373 539 849

1348 2123 3372 4255 5358 6755 7964 9520

Reduce lengths by 13% for 200 V systems.

Lengths in bold require 90ºC wire. Shading indicates 40º C

maximum ambient.
* Wire does not meet the N.E.C. ampacity requirement.

Maximum Cable Lengths in Feet to Limit Voltage

Drop to 5% for 230 V Systems

Copper Wire Size 75ºC Insulation Exposed to a Maxi-

mum of 50ºC (122ºF) Ambient Temperature

Units with 1Ø Input and

3Ø Output (Motors)