Aquavar solo – user interface board, Quick s tar t guide – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual

Page 95

Advertising
background image

QUICK

S

TAR
T GUIDE

91

Aquavar SOLO –

User Interface Board

1AS Controllers

3AS Controllers

Pressure Ranges for All Available Transducers

transducer

1AS15 / 3AS20

3AS30

3AS50

(min. PSi)

(max. PSi)

(min. PSi)

(max. PSi)

(min. PSi)

(max. PSi)

100 PSI

(1)

20 85 20 85 10 50

200 PSI

(2)

40 170 40 170 20 100

300

PSI 60 255 60 255 30 150

(1) Standard on 1AS15, 3AS20 and 3AS30

(2) Standard on 3AS50

Service Factor Amps – All Motors

Drive

Settings /

Protection

Pressure

Adjustment

Pressure

Transducer

Connection

Current Limit Dial

(Motor Overload Protection)

Switch Input

(Over

Pressure Protection,

Level Control)

trANSDuCer

JumPer

230 Volt

200 Volt

HP

1Ø 2-Wire

1Ø 3-Wire

CentriPro

1

Franklin Grundfos CentriPro

1

Franklin Grundfos CentriPro Franklin Grundfos CentriPro Franklin

½

4.7/4.7 6 6 6.3/6.1 6 6 N/A N/A N/A N/A N/A

¾

6.4/6.2 8 8.4 8.3/7.8 8 8.4 3.9 3.8 N/A 4.5 4.4

1

9.1/8.1

9.8 9.8

9.7/9.4

9.8 9.8 4.7 4.7 N/A 5.5 5.4

1½ 11.0/10.4 13.1

2

13.1

2

11.1/10.9

11.5 11.6 6.1 5.9 7.3 7.2 6.8

2 N/A N/A N/A 12.2 13.2

2

13.2

2

7.6 8.1 8.7 8.8 9.3

3 N/A N/A N/A N/A N/A N/A 10.1 10.9 12.2 12 12.5

5 N/A N/A N/A N/A N/A N/A 17.5 17.8 19.8

2

20.2

2

20.5

2

1. CentriPro 2-Wire motors have Generation 1 and Generation 2 amp ratings, see motor nameplate or motor data sticker that was supplied with motor.
2. Amps are higher than controller overload range - use of these motors will current limit and provide reduced performance.

93