Aquavar abii quick start guide, Quick s tar t guide – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual

Page 96

Advertising
background image

94

Aquavar ABII Quick Start Guide

Installation Steps:

1. install the Pump

• Plumb suction and discharge of pump into piping.
• Install a check valve on the suction side.
• Locate the pump as near liquid source as possible.

2. install the Pressure transducer

• Install the pressure transducer in the tank tee provided with

the unit.

• Locate the transducer within 120” of the controller.

3. mount the Controller

• Mount vertically in a well ventilated, shaded area with 8

inches of free air space on every side and temperature
between 34º F and 104º F.

4. Connect input Power

• Connect the 1Ø power from a 20 amp 2-pole circuit breaker.
• Do not use GFCI protection with ABII as nuisance tripping

will result.

5. Output Power Connections

• Connect the output power leads from the controller to the 3

motor leads in the conduit box on the motor.

6. Set the motor Overload Switches (or dials, 3 and 5 HP)

• Complete systems have overloads pre-set at factory.

7. Set the Pressure - Factory pre-set is 50 PSi

• Push and Hold the Increase or Decrease Pressure Adjust

Pushbutton until the desired pressure setting is reached.

• The maximum allowable pressure setting is 85 psi.

8. Set the Application Switches (or dials, 3 and 5 HP)

• Minimum Speed of 10 Hz – the incoming pressure is within 20

PSI of the desired pressure setting.

• Minimum Speed of 30 Hz – the incoming pressure is 20 PSI or

more below the desired pressure, if pumping from a tank or if
drawing a suction lift.

• Ramp Speed – Slow - Low flow; Medium - Medium flow; Fast

- High flow

QUICK

S

TAR

T GUIDE

Advertising