Cont a c tor check out – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual
Page 18
Advertising
![background image](/manuals/310401/18/background.png)
Additional information on troubleshooting
and replacement parts for 1Ø Control Boxes
is available in the MAID; Motor Application
and Installation Manual. It is also available
online at www.xyleminc.com/brands/
gouldswatertechnology.
Checkout Procedure
for Magnetic and Other
Contactors
Contactor Coil Test
(Disconnect lead from one side of coil)
1. Meter setting: R X 100
2. Connections: Coil terminals
3. Correct meter reading: 180 to
1,400
ohms
Contactor Contact Test
1. Meter Setting: R X 1
2. Connections: L1 & T1 or L2 & T2
3. Manually close contacts
4. Correct meter reading: Zero ohms
C
ONT
A
C
TOR CHECK
OUT
16