Transformer sizes – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual

Page 92

Advertising
background image

Transformer Capacity Required

for Submersible Motors

A full 3Ø supply is recommended for all 3Ø

motors, consisting of three individual transformers

or one 3Ø transformer. “Open” delta or wye con-

nections using only two transformers can be used,

but are more likely to cause problems from current

unbalance.
Transformer ratings should be no smaller than

listed in the table for supply power to the motor

alone.

Smallest KVA Rating -

Submersible

Total

Each Transformer

3Ø Motor

3Ø Motor Open WYE

WYE

HP Rating

HP Rating

or Delta 2

Delta 3

Transformers Transformers

1.5

3

2

1

2

4

2

1.5

3

5

3

2

5

7.5

5

3

7.5

10

7.5

5

10

15

10

5

15

20

15

7.5

20

25

15

10

25

30

20

10

30

40

25

15

40

50

30

20

50

60

35

20

60

75

40

25

75

90

50

30

100

120

65

40

125

150

85

50

150

175

100

60

175

200

115

70

200

230

130

75

90

TRANSFORMER SIZES