Qvr • cp ∆t – Xylem Fire diesel pump D Series GEN D Series User Manual

Page 47

Advertising
background image

47

In environments containing airborne particles, install pre-filtering systems to prevent clogging

of the radiator filters.

The fresh air needed to ensure proper air flow is delivered through openings located at the

bottom of the room and, whenever possible, in the wall opposite the radiator, so that the

fresh air flows around the entire engine before being expelled by the fan.

For safety purposes, in the case of continuously operating diesel pumps installed in an

enclosed environment, and for applications with high ambient temperatures, you should

make sure that the cooling air reaching the radiator does not exceed the admissible

temperature for the radiator. If the temperature of the air reaching the radiator needs to be

lowered, we recommend using an auxiliary extractor fan whose capacity must be calculated

using the same formula utilized for verification, adopting the maximum ΔT value that enables

proper operation of the radiator based on the values declared by the engine manufacturer.

Position the extractor fan higher up on the same wall through which the vent discharges the

hot air; the extractor must guarantee a head exceeding the vacuum created in the room by

the radiator fan.

Use the following formula for verification:





Q= Total heat input into the room, including engine radiance, expressed in [kcal/h]

Cp = Specific heat of air at constant pressure expressed in [kcal/m3 °C] , the value is obtained

from the normogram shown below.

Vr = air capacity of engine radiator fan in [m3/h]


Δ

T = Tv-Ta= difference between the temperature of the air affecting the radiator (Tv) and

the temperature of the outdoor air supplied to the room (Ta) expressed in [°C]

Q

Vr • Cp

∆T =

Advertising