51

Protect the exposed cables from accidental knocks or damage. Protect the power line

according to the regulations in force.

Use cables suitable for the type of installation, according to the regulations in force.

GROUNDING

The metal parts of the system that are subject to contact with people, and which as a result

of faulty insulation or any other cause could be energized, must be connected to a ground

plate. The panels are provided with a suitable grounding terminal. The connection cable to

the ground plate and the related contact resistance must be sized according to the

regulations and standards in force. If necessary, unipotential connections can be made, and

the base can be connected directly to the ground.

FIRE DIESEL PUMP ELECTRICAL CONTROL PANEL

The electrical control panel is pre-connected to the diesel pump. Refer to the wiring diagram

supplied together with the electrical panel for the connection of :


-

Starting devices ( pressure switch and/or level switch)

-

Alarm signalling devices

Level switch connection:

The level switch installed in the priming tanks for suction lift sets is designed to start the

diesel pump when the water level in the tank drops.

The level switch connection terminals are normally jumpered to enable operation. When

installing the level switch, make sure you remove the jumper found on the terminals.

The panel features clean contacts for signalling purposes, suitable for connection to alarms

and/or remote signalling devices, for the main functions:
-

Programmed alarm output

-

Automatic selector switch disabled

-

Failure to start

-

Engine running

-

Control unit failure

-

Low fuel level

-

Alarm

The electrical panel installation and maintenance operations may be performed by

qualified electricians only!

The diesel pump is an automatic starting machine that can start up even in the

absence of any voltage in the panel!