The starting sequence in MANUAL MODE is as follows:

1. Selector switch set to MAN position

2. Press the START button on the board which commands the starting motor. Each time you

press the button the selection of the start battery changes by closing the corresponding

starting relay contact.

If the engine starts and the operator keeps holding down the button, the control board

commands the automatic disconnection of the starting motor.

If the engine is running (pump running indicator light on) the starting motor does not

activate.

If the engine does not start immediately, there is no maximum time limit for Manual

starting, it is up to the operator.

3. With the engine running, the board checks the rpm’s and, if they exceed the starting

threshold, the pump-running indicator light comes on (indicated on the display) and the

starting motor is disconnected.

Here you can note down the necessary data as shown on the rating plate. Specify this data

when you call for service.

Engine type (engine rating plate)

Engine serial number (engine rating plate)

Pump type (pump rating plate)