The starting sequence in MANUAL MODE is as follows:
1. Selector switch set to MAN position
2. Press the START button on the board which commands the starting motor. Each time you
press the button the selection of the start battery changes by closing the corresponding
starting relay contact.
If the engine starts and the operator keeps holding down the button, the control board
commands the automatic disconnection of the starting motor.
If the engine is running (pump running indicator light on) the starting motor does not
activate.
If the engine does not start immediately, there is no maximum time limit for Manual
starting, it is up to the operator.
3. With the engine running, the board checks the rpm’s and, if they exceed the starting
threshold, the pump-running indicator light comes on (indicated on the display) and the
starting motor is disconnected.