FIRE DIESEL PUMP ELECTRIC PANEL

Technical characteristics

-

Single-phase

alternating

power

supply voltage: 230Vac 50/60 Hz;

-

Battery voltage 12/24Vdc (selectable

from the control unit);

-

Protection class: IP54 (IP55 option);

-

Fuse for battery charger and heater

supply line protection;

-

Automatic battery chargers with

buffer charge;

-

Steel structure painted Dimensions

500x350x200 mm.

1 - Electric control unit

Display of alarms and status, battery voltage,

revolution counter, hour counter, alarm

programming, dater, main signals and manual

start button.

2 - Key-operated 3-position selector switch

“Manual - Automatic- 0ff“

Manual mode: Enabling of START/STOP/ENTER

pushbuttons on the control unit, with possibility of starting and stopping the engine. When

the engine is stopped, you can access the set-up configuration.

Automatic mode: the engine is started via a pressure switch. Manual stopping with the

exception of UNI 10779 fire diesel pump version for fire-hydrant networks.

Shutdown mode “0”: the diesel pump cannot be started manually or automatically from the

electronic control unit. The set up configuration can't be accessed in this mode. Alarms can

be reset using the RESET button for 5 sec, provided that the problem that triggered the alarm

has been eliminated.

3 (4) - Battery emergency start button 1(2)

This button starts the engine directly from battery 1 (2) in case of an emergency

5 - Main switch

Switch for power supply from the line

OPERATING MODE: REFER TO FIRE DIESEL PUMP ELECTRONIC CONTROL UNIT
MANUAL

EMERGENCY OPERATING MODE

Use only in case of automatic or manual system failure.

Key-operated selector switch set to AUTOMATIC or MANUAL or STOP position