FIRE DIESEL PUMP ELECTRIC PANEL
Technical characteristics
-
Single-phase
alternating
power
supply voltage: 230Vac 50/60 Hz;
-
Battery voltage 12/24Vdc (selectable
from the control unit);
-
Protection class: IP54 (IP55 option);
-
Fuse for battery charger and heater
supply line protection;
-
Automatic battery chargers with
buffer charge;
-
Steel structure painted Dimensions
500x350x200 mm.
1 - Electric control unit
Display of alarms and status, battery voltage,
revolution counter, hour counter, alarm
programming, dater, main signals and manual
start button.
2 - Key-operated 3-position selector switch
“Manual - Automatic- 0ff“
Manual mode: Enabling of START/STOP/ENTER
pushbuttons on the control unit, with possibility of starting and stopping the engine. When
the engine is stopped, you can access the set-up configuration.
Automatic mode: the engine is started via a pressure switch. Manual stopping with the
exception of UNI 10779 fire diesel pump version for fire-hydrant networks.
Shutdown mode “0”: the diesel pump cannot be started manually or automatically from the
electronic control unit. The set up configuration can't be accessed in this mode. Alarms can
be reset using the RESET button for 5 sec, provided that the problem that triggered the alarm
has been eliminated.
3 (4) - Battery emergency start button 1(2)
This button starts the engine directly from battery 1 (2) in case of an emergency
5 - Main switch
Switch for power supply from the line
OPERATING MODE: REFER TO FIRE DIESEL PUMP ELECTRONIC CONTROL UNIT
MANUAL
EMERGENCY OPERATING MODE
Use only in case of automatic or manual system failure.
Key-operated selector switch set to AUTOMATIC or MANUAL or STOP position