If the set has been out of operation for a long time, especially in a humid environment, you

should check the ground isolation of the electrical panel and make sure the auxiliary circuits

are properly supplied with power. ( Refer to the panel wiring diagram)

FIRST COMMISSIONING

Once the preliminary operations described above have been carried out, proceed as follows:

Clean the set and its surrounding area thoroughly, removing all stains and dirt, oils,

fuels, thinners, etc..

Make sure there are no rugs, bits of paper or other lightweight materials near the air

suction inlets.

Make sure there are no foreign bodies near the rotating parts.

Stow all the tools and rags in the appropriate storage containers.

For firefighting diesel pump according to EN12845:2004.

Set the key-operated selector switch to MANUAL mode and follow the instructions

provided in the control unit manual.

The diesel pump begins its automatic startup cycle with the fuel supply turned off. Six

automatic startup attempts will be made, each lasting no less than 15 seconds, with the

starter in ON mode and with 10 and 15 second intervals. After the six attempts, a failure

to start alarm will be triggered. Restore the fuel supply and press the START button on

the control unit.

Switch off the diesel pump by setting the key-operated selector switch to the “0”

position

For diesel pump for civil applications.

Start the diesel pump by setting the key-operated selector switch to the MANUAL

position (the diesel engine will start automatically a few seconds later, reaching steady

state speed immediately)

Switch off the diesel pump by setting the key-operated selector switch to the “0”

position

Make sure there are no leaks in the water, oil and fuel circuits.

With the engine running, simulating the triggering of the sensors on the terminals, check

the correct operation of the protections against low oil pressure, high engine

temperature and charge generator failure, referring to the operating logics in the wiring

diagrams and the relevant standards (procedure for qualified personnel only).

For the diesel pumps according to UNI standards, check the correct operation of the

alternance for the starting batteries.

As regards the following checks concerning correct operation, refer also to the section

containing the instructions for users, which illustrates in detail the different operating modes

and related controls.

Check the automatic starting procedure: set the key-operated selector switch to the

AUTOMATIC position and simulate the triggering of the starting device on the terminal

board. If possible, the pressure drop should be simulated directly on the starting pressure

switch. To switch off the diesel pump after start-up, return the key-operated selector

switch to the STOP position

One by one, check the proper operation of the EMERGENCY START BUTTONS. Warning:

after starting with the emergency button the diesel pump can be switched off only by

manually operating the stop lever situated on the engine (electric stop device).