Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 14

Advertising
background image


14

5 Technical Data

HYDROVAR

Incoming power supply (data only for dimensioning of the power

supply line and not for calculating the efficiency of the HV)

type rated

output

Voltage limits

48-62 Hz

nominal

current input

recommended

line protection

maximum

cross-section

HV [kW]

[V]

[A]

[A]

[mm²]

2.015 1,5

14,0

20

2.022 2,2

1~230 ± 15%

20,0 25

4

4.022 2,2

7,4

13

4.030

3

9,1

13

4.040 4

3~380-460 ± 15%

11,7 16

4

4.055 5,5

17,5

20

4.075 7,5

22,1

25

4.110 11

3~380-460 ± 15%

29,9 32

4

4.150 15

39,0

50

4.185 18,5

48,1

50

4.220 22

3x380-460 ± 15%

55,9 63

25

HYDROVAR

Output to the motor

type rated

output

max. output voltage

nominal

current output

motor connection cables

HV [kW]

[V]

[A]

mm²

2.015 1,5

7,0

2.022 2,2

3x U

in

10,0

4x1,5 – 4x4

4.022 2,2

5,7

4.030 3

7,3

4.040 4

3x U

in

9,0

4x1,5 – 4x4

4.055 5,5

13,5

4.075 7,5

17,0

4.110 11

3x U

in

23,0

4x2,5 – 4x4

4.150 15

30,0

4.185 18,5

37,0

4x6 – 4x25

4.220 22

3x U

in

43,0

4x10 – 4x25

Make sure that the electrical data of the HYDROVAR match those of the
electric pump. Improper combinations may cause errors and malfunction of
the protection of the electric motor.

The nominal current of the motor must be lower than the rated current of the
HYDROVAR to prevent overheating or shutdown due to OVERLOAD.

The max. output current of the HYDROVAR could reach 110% of the nominal current for
max. 60 sec. before the error OVERLOAD will occur.