0400 0400 SUBMENU SENSOR

In this submenu all actual value sensors which are connected to the HYDROVAR can be

configured, (up to two transducers with current output or voltage signal output).

It is not possible to install two different transducer types because main configuration is the
same for all connected sensors. Transducers must be always the same type.

0405

0405 DIMENS. UNIT

Bar

Dimension unit

Possible settings: bar, psi, m

3

/h, g/min, mH2O, ft, °C, °F, l/sec, l/min, m/sec, …, %


Chose the desired dimension unit by pressing

or

▼.

By changing the DIMENSION UNIT, you have to consider changing the SENSOR RANGE
[0420] according to the new DIMENSION UNIT too!

0410

0410 CONF SENSOR

Sensor 1

Selection of the sensor

Possible settings: - Sensor 1

- Sensor 2

- Auto

- Switch Dig1

- Switch Dig2

- Switch Dig3

- Switch Dig4

- Auto Lower

- Auto Higher

- (Sensor 1 – Sensor 2)

This parameter determines how the connected sensors are used and which one is active.
It is also possible to measure the difference of two connected sensors or to configure an
automatic switchover in case of a faulty sensor.

Sensor 1

Sensor 1 is constantly active.
0/4-20mA signal ……. connected to X3/2 and X3/3 (+24V)
0-10V signal ……. connected to X3/6 and X3/3 (+24V)

Sensor 2

Sensor 2 is constantly active.
0/4-20mA signal ……. connected to X3/4 and X3/3 (+24V)
0-10V signal ……. connected to X3/5 and X3/3 (+24V)

Auto

Automatic switch over in case of a faulty transmitter.

Switch Dig1

Manual switching by closing digital input 1 (X3/9-10)

Switch Dig2

Manual switching by closing digital input 2 (X3/6-GND)

Switch Dig3

Manual switching by closing digital input 3 (X3/5-GND)

Switch Dig4

Manual switching by closing digital input 4 (X3/15-GND)

Auto Lower

The sensor with the lower actual value (or available sensor in case of a
faulty sensor) is used automatically

Auto Higher

The sensor with the higher actual value (or available sensor in case of a
faulty sensor) is used automatically

Sens.1 – Sens.2 The difference of both connected sensors is taken as actual value