Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 89

Advertising
background image


89

1000 1000 SUBMENU TEST RUN

1005

1005 TEST RUN

after 100 hrs

Automatic test run

Possible settings:

OFF – 100 h.

The Automatic Test Run starts up the pump after the last stop to prevent the pump from
blocking.
Test Run Time, Frequency and Boost can be selected in the parameters below.

To disable the automatic test run, press

until OFF appears on the display.


The test run is only active when the HYDROVAR is stopped but manually released and
external ON/OFF contact (X3/7-8) is closed!

1010

1010 TESTRUN FRQ.

30.0 Hz


Frequency for manual and automatic test run

Possible settings:

0 – Fmax

1015

1015 TESTR. BOOST

10.0 %.

Setting of the motor starting voltage in % of rated
input voltage

Possible settings:

0 – 25% of maximum input voltage is possible

1020

1020 TESTR. TIME

5 sec

Test Run time

Possible settings:

0-180 sec.

1025

1025 SEL. DEVICE

01

Select Inverter for manual test run

Possible settings:

01-08

1030

1030 TESTRUN MAN

Press

3 sec.

Manual Test Run, Confirm test run for selected unit


With this parameter it is possible to perform a manual Test Run for one selected unit. (Even
fixed speed pumps in Cascade Relay Mode can be included into the test run function)
By pressing

button for approx. 3 sec. a test run will be started.