0200 SUBMENU CONF

INVERTER

0202

0202 SOFTWARE

HV V01.4

Software version of the control board

If a Remote Display is connected also its software version is shown in this window.

0202

0202 SW RD V01.0

HV V01.4

Software version of the Remote display (RD) and the

control board (HV)

0203

0203 SET VER.INV

sel:00 act:00

Selection of the SW version on the power board

Possible settings:

00 - 02

Manual selection of the required (sel.) and indication of the active (act.) software version
on the power board.
All available versions can be selected if version of BASIC is production date > 05/2008.
After pressing

button for 5 seconds the selected specification is activated and DONE is

displayed.
Following parameters [0285], [0286], [0290] and [0291] are added to the menu (only on
units 5.5-22kW!)

The required version can only be activated if all devices are updated to the new version;

else version will be automatically re set to the next lower version.

Setting 00: all units with production date prior 05/2008
Setting 01: BASIC 1.5-4kW (starting with control board software V01.3 see [47]
Setting 02: BASIC 5.5-22kW (starting with control board software V01.3

0205

0205 MAX. UNITS

06


Maximum number of units

Possible settings:

1 - 8


Select: The maximum number of units which can operate at the same time.


For example:
Cascade Serial:
1 MASTER - and 2 BASIC Inverters are installed in a multi-pump-system

Æ

reasonable values = 1…3

Cascade Relay:
1 MASTER Inverter and 3 fixed speed pumps -> reasonable values = 2…4