03 EFF REQ VAL

D1 X.XX Bar

Effective required value

Shows the current required value that is calculated based on ACTUAL VALUE INCREASE

[0505], ACTUAL VALUE DECREASE [0510] and LIFT AMOUNT [0330]. If the required value is
influenced by an offset signal (SUBMENU OFFSET [0900]) the current active required value

is also shown in this window.

E.g. Multi-pump-application with two pumps

REQUIRED VALUE [02]:

5.00 bar

ACT. VALUE INCREASE [0505]:

0.50 bar

ACT. VALUE DECREASE [0510]:

0.25 bar

->

REQ VAL EFF [03]:

5.25 bar


After starting the second pump the pressure will be increased to a system pressure of 5.25

bar. With this parameter you are able to see the calculated new required value.

c) Active MODE [0105] = Actuator

Frequency XX.X Hz

STOP X.XX Bar

1

st

display in Mode actuator


If parameter MODE [0105] is set to actuator the parameter REQUIRED VALUE [02] will
change to ACTUAT. FREQ. and is equivalent to parameter [0830].
By using this parameter it is possible to run the HYDROVAR up to two pre-selected
frequencies to manually control the HYDROVAR.

02

02 ACTUAT.FRQ.

D1 XX.X Hz

Set the desired frequency with either

or

The selected frequency in this parameter is only active in the actuator mode. The
configuration must be done with parameter C.REQ.VAL.1 [0805] or C.REQ.VAL 2 [0810]
and parameter SW REQ.VAL [0815].
For manual setting of the frequency the parameters ACTUATOR FREQUENCY 1 [0830] and
ACTUATOR FREQUENCY 2 [0835] can be used.
For detailed information how to run the HYDROVAR by manual control, see submenu
REQUIRED VALUES [0800].


Parameter [03] is not shown in Mode - Actuator