Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 47

Advertising
background image


47

Control Terminals
All control cables connected to the control-unit have to be screened (See chapter 9.3

recommended cable types).
External volt free contacts must be suitable for switching <10 VDC.

NOTE:
If unscreened control cables are used, signal interference may occur and
could interfere with incoming signals and the function of the HYDROVAR.

Don’t connect the ground of the control card to other voltage potentials.
All electronic ground terminals and GND of the RS 485-interface are connected internally.

X3 Digital and Analogue I/O

1 GND, electronic ground

2 Actual value input sensor 1

0-10VDC or 0-20mA / 4-20mA [Ri=50Ω]

3 Power supply for external sensors

24VDC, max. 100mA

4 User SIO-Interface: SIO-
5 User SIO-Interface: SIO+
6 GND, electronic ground


User Interface for external usage

7 External ON/OFF (release)

active low

8 GND, electronic ground

9 Configurable digital input 1

active low

10 GND, electronic ground

11 Low water

active low

X3/

12 GND, electronic ground


Low water

e.g. incoming pressure switch or water level switch required.


Configurable digital input 1

e.g. to enable 2nd required value


External ON/OFF (release)

GND, electronic ground

User SIO-Interface: SIO+

User SIO-Interface: SIO-

Sensor supply

max. 100 mA

Actual-value input sensor 1

0-10V or 0-20mA / 4-20mA [Ri=50Ω]

Ground