0500 SUBMENU

SEQUENCE CNTR.


Using the parameters of this submenu, all necessary settings can be done for running a

multi-pump system (even in cascade relay and cascade serial / synchron mode).

Application Example:
1) Lead pump reaches its ENABLE FREQUENCY [0515]

2) Actual value falls and reaches the cut in-value of the 1

st

assist pump

Cut in-value = REQUIRED VALUE [02] – ACT. VAL. DEC. [0510]
Î

the 1

st

assist pump is switched on automatically


3) After the start up the new required value is calculated in the following way:

NEW REQUIRED VALUE = REQ.VAL. [02] – ACT.VAL.DEC [0510] + ACT.VAL.INC. [0505].
The new required value is shown in the main menu as parameter EFF.REQ.VAL. [03].











Calculations of the new required value for multi pump applications:

k ... number of active pumps (k >1)
p = p

set

+ (k-1)*[lift value – fall value]

• Lift value = Fall value ⇒ Pressure constant independent how many pumps are in

operation

• Lift value > Fall value ⇒ Pressure rises when assist pump switches on
• Lift value < Fall value ⇒ Pressure falls when assist pump switches on