Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 56

Advertising
background image


56

20

20 SUBMENU STATUS

Status of all units within a pump group

Using this submenu it is possible to check the status (including failures and motor hours) of

all connected units.

21

21 STATUS UNITs

00000000


Status of all units


This parameter gives a quick overview about the status of the connected units

- In

Cascade serial/synchron mode the status of all (max. 8) connected units is shown

(whereas 1=activated / 0=deactivated)

-

In Cascade relay mode (MASTER is equipped with additional Relay Card) the status
of the 5 Relay- switching contacts is shown.

E.g. Mode – Cascade serial/synchron

21 STATUS UNITs

11001000

Unit 1, 2 and 5 are running


E.g. Mode – Cascade relay

21 STATUS UNITs

10100 - - -

Relay Contact 1 and 3 are closed

22

22 SELECT DEVICE

* 1 *

Select device

Possible settings:

1-8


Check the current status, the motor hours and the last failures which occurred.
The selection is depending on the selected mode [105].
Select desired unit by pressing

or

▼.


Mode CASCADE SERIAL/SYNCHRON:
The selection specifies the address of the HYDROVAR units
E.g. Device 1 -> MASTER Inverter with pre-selected address 1

Device 2 -> BASIC Inverter with pre-selected address 2

Device 3 -> BASIC Inverter with pre-selected address 3


For set the address on a BASIC Inverter, see chapter addressing.
To set the address on a MASTER Inverter, see parameter [106] or submenu [1200] RS485-
Interface.

S

S

G

G

G