Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 86

Advertising
background image


86

0900 0900 SUBMENU OFFSET

The different analogue inputs on terminals X3/13-24 can be used also to connect a second
actual value signal as offset source for the required value.

0905

0905 OFFS. INPUT

OFF

Selection of the Offset Input

Possible settings:

OFF

analog U1 0-10V

analog U2 0-10V

analog I1 0-20mA / 4-20mA analog I2 0-20mA / 4-20mA

OFF

Offset disabled

analog U 1

0-10V

Offset will be calculated according to the voltage signal (0 – 10V)
connected to terminals X3/13 (Required Value 1) - X3/14 (GND).

analog U 2

0-10V

Offset will be calculated according to the voltage signal (0 – 10V)
connected to terminals X3/15 (Required Value 2)- X3/16 (GND)

analog I 1

0/4 – 20mA *

Offset will be calculated according to the current signal (4 – 20mA or
0 – 20mA) connected to terminals X3/18 (Required Value 2) - X3/17 (GND).

analog I 2

0/4 – 20mA *

Offset will be calculated according to the current signal (4 – 20mA or
0 – 20mA) connected to terminals X3/23 (Required Value 2) - X3/22 (GND).

• Notice: If the incoming current signal drops below 4mA, a warning message is shown

on the display but the HYDROVAR keeps operating without the Offset function.

0907

0907 OFFSET RANGE

100

Representation of the sensor range

Possible settings:

0 – 10000

The Offset Range can be set to a number between 0 and 10000. Its value depends on the
maximum range of the connected offset sensor. Settings of the x- axis are shown in the

chart below.
E.g.: 16 bar sensor can be set as range: 16; 160; 1600

The higher the set offset ranges the higher is the resolution on the signal input.