0275 POWER REDUCT.

OFF


Reduction of the maximum output current

Possible settings:

OFF, 85%, 75%, 50%

If a motor with lower nominal power is used, the maximum output current should be
adjusted accordingly.
The reduction of the maximum output current also affects the overload-detection!

Output current [A]

HV type

OFF = 100%

85%

75%

50%

2.015 7,00 5,95 5,25 3,50
2.022 10,00 8,50 7,50 5,00
4.022 5,70 4,85 4,28 2,85
4.030 7,30 6,21 5,48 3,65
4.040 9,00 7,65 6,75 4,50
4.055 13,50 11,48 10,13 6,75
4.075 17,00 14,45 12,75 8,50
4.110 23,00 19,55 17,25 11,50
4.150 30,00 25,50 22,50 15,00
4.185 37,00 31,45 27,75 18,50
4.220 43,00 36,55 32,25 21,50

0280

0280 SEL.SW.FRQ.

Auto

Selection of the switching frequency

Possible settings:

Auto, 8 kHz, 4 kHz

Auto (default setting)
In standard operation the HYDROVAR works with a switching frequency of 8kHz in order to
reduce the noise level. At rising temperature inside the HYDROVAR the switching frequency
is decreased to 4kHz automatically.
8 kHz - Selection with lowest noise level, but without decrease at rising temperature.
4 kHz - Reduce the temperature in the HYDROVAR