Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 94

Advertising
background image


94

11.2 MASTER / SINGLE Inverter
Each error is shown on the display in plain text and saved in the error memory.

The errors can be reset automatically (depending on the setting in parameter ERROR-RESET
[0615]) or manually in following ways:


• cutting the power supply for > 60 seconds
• pressing

and

simultaneously for about 5 seconds

• open and close the External ON/OFF (Terminals X3/7-8)


No error-message on the display

Error

probable cause

measure

no AUTOSTART after
power failure

Parameter AUTOSTART [08] is
set to OFF

Check parameter AUTOSTART [08]

No operation even system
pressure < set pressure

Pressure higher than the start
value or REGULATION MODE
has been changed to
INVERSE.

check parameter START VALUE [04]
and/or REGULATION MODE [0320]



Error-message on the display

Error

probable cause

measure

OVERCURRENT

ERROR 11

Current rise at the output too
high

• check connection-terminals of the

HYDROVAR

• check the connection-terminal of

the motor and the motor-cable

• check the windings of the motor

Reset:

• cutting of the power supply for >60 seconds.
• automatic Error-reset not possible for that kind of failure!








Advertising