Actuator: (For SINGLE pump operation only!)
The actuator mode has to be used if a fixed speed setting is required or an external speed

signal is connected and the HYDROVAR is just used like a standard VFD.

In this case, the internal controller is shut off, so the HYDROVAR does not control the set
value but runs the connected motor at a frequency proportional to the input signal which
is connected to the analogue inputs or is set directly on the HYDROVAR.

• A manual switching between the analogue inputs is possible by using the corresponding

digital inputs.


• The frequency varies along the programmed Ramps 1 (accelerative) and 2 (declarative).

The functions thermal protection and external ON/OFF remain still active.


• The functions External ON/OFF, Motor Overheat, Lack of water and all other internal

protections still work.


In the actuator mode it is also possible to work with pre-selected frequencies for a manual
control of the HYDROVAR. It is possible to set two different frequencies in the submenu

REQUIRED VALUES [0800]. A changeover of these frequencies can be done with parameter
SW REQ. VAL [0815].

X3/13: Voltage signal input (Required value 1)

0-10V

0 - MAX.FREQ.[0245]

X3/15: Voltage signal input (Required value 2)

0-10V

0 - MAX.FREQ.[0245]

X3/18: Current signal input (Required value 1)

4-20mA

0 - MAX.FREQ.[0245]

0-20mA

0 - MAX.FREQ.[0245]

X3/23: Current signal input (Required value 2)

4-20mA

0 - MAX.FREQ.[0245]

0-20mA

0 - MAX.FREQ.[0245]

range of control

zeropoint

max

min

*

range

signal

+

=