If the MASTER Inverter goes below that frequency for longer than the pre-selected DISABLE
DLY [0535] and the system pressure is higher than the EFFECTIVE REQ. VALUE [03]

(REQUIRED VALUE [02] + ACTUAL VAL. INC [0505]), the first assist pump stops.

0535

0535 DISABLE DLY

5 sec

Disable delay time (for cascade relay only!)

Possible settings:

0 – 100 sec


Delay time before switching off the assist up pumps in cascade relay mode.

0540

0540 DROP FRQ

42 Hz

Drop frequency (for cascade relay only!)

Possible settings:

0.0 – 70.0 Hz


This parameter is used to prevent the system from pressure hammers. Before a following
pump starts up, the MASTER Inverter will drop to the selected frequency. If the DROP
FREQUENCY is reached, the follow-up-pump gets released and the MASTER Inverter will
continue with normal operation.

0545

0545 OVERVALUE

OFF

Overvalue (for cascade relay only!)

Possible settings:

OFF – pre selected sensor range

If this selected value is reached, an immediate shut-off of the follow-up-pumps is executed.

E.g. REQUIRED VALUE [02]:

5.00 bar

OVERVALUE

[0545]:

7.50

bar

If three pumps are running (1 MASTER Inverter + 2 follow-up-pumps) and a system
pressure of 7.50 bar is reached, one after another assist pump is switched off.

This parameter prevents the system against overpressure in case the HYDROVAR has been
parameterized incorrectly.

0550

0550 OVERVAL DLY

0 sec

Overvalue delay (for cascade relay only!)

Possible settings:

0.0 – 10.0 sec

Delay time to switch off an assist pump in case the actual value exceeds the
OVERVALUE [0545] limit.