Error

probable cause

measure

OVERLOAD

ERROR 12

Power limit of the HYDROVAR
is exceeded

• check Parameter RAMP 1/2

[0215/0220] (too short) and BOOST
[0265] (too low)

• check motor connection

(star/delta) and cable

• Pump blocked
• Motor turns in the wrong direction
before running
(Non return-valve defect)

Not allowed operation point or
MAX. FREQUENCY [0245] too high
check also the BOOST [0265].

OVERVOLTAGE

ERROR 13

DC voltage of the HYDROVAR
too high

• Parameter RAMP 2 [0220] too fast

• Power supply too high

• Voltage peaks too high
• (Solution: Line filters, Line

inductance, RC-element)

INVERT. OVERHEAT

ERROR 14

too high temperature inside
the HYDROVAR

• no proper cooling
• contamination of the motor vents
• ambient temperature too high

THERMO MOT/EXT

ERROR 15

An external protective device
connected to terminal X1/PTC
has released (e.g. PTC which is
connected has reached its
release temperature)

• close X1/PTC if there is no external

protective device connected

• close external on/off switch if

connected to these terminals

• For detailed information how the

terminal X1/PTC could be used see
chapter 9.4.3

PHASELOSS

ERROR 16

One phase

of the power supply

has been lost -> automatic
power reduction (just available
for the units HV4.055-4.220)

• check power supply under full load

– check if phase failure at the input

• check circuit breakers
• visual inspection of points at the

input terminals

UNDERVOLTAGE

DC voltage of the HYDROVAR

too low

• supply voltage too low
• phase failure at the input
• asymmetry of the phases

COMM LOST

The communication between

the Power Unit and the control

card doesn’t work correctly

• check if the addressing of BASIC

Inverter [DIP SW.] has been done
correctly (retry!)

• check if each unit has allocated its

own pump address

• check if the connection from

control card to the power unit is
made properly (ribbon cable)