If the HYDROVAR is used as a

BASIC Inverter in a multi-pump system, the internal interface

on the power unit is used for the serial RS-485 connection to the other HYDROVAR units in

the system. (Be careful: Internal interface is not available in SINGLE Inverter configuration!)

X2 RS485-Interface – Power Unit

SIO -

Internal SIO-interface: SIO-

SIO + Internal SIO-interface: SIO+

X2/

GND

GND, electronic ground

Internal interface
for multi-pump-systems

……. Parameter not available for a HYDROVAR SINGLE Inverter


The internal RS-485 Interface on the power unit is used for the communication between
up to 8 HYDROVARs in a multi-pump system (minimum 1 MASTER Inverter). For the
connection to each HYDROVAR via the RS-485 interface the terminals X2/1-3 on the power

unit can be used twice. Or the terminals X4/4-6 on the control card can be used.




RS485 – internal interface




Mechanical connection of the terminal:
- Use recommended cable type (see chapter 9.3)
- Strip the end of the used wire (about 5 … 6mm)
- push down the orange wedges by using a small screwdriver
- insert the stripped wire
- remove the screwdriver to fix the wire

- To remove, push down the orange wedges and pull out the wire!


Connection example using one MASTER - and three BASIC - Inverters: