9.4.3.2 Addressing
When using the cascade serial/synchronous mode in a multi-pump-application (where more
than one MASTER Inverter or even BASIC Inverters are used), the right address must be set

to ensure a proper communication within the system.

MASTER Inverter – The desired address

of the MASTER Inverter has to be set via the

HYDROVAR-software. In this case for all MASTER Inverters the below shown dip-switch on
the power unit must be set to address 1 (default setting).

BASIC Inverter (not standard use for HV 4.150-4.220)

– when using a BASIC Inverter in a

multi-pump-system it is necessary to set the dip-switches on the power unit in order to get

a separate address for each Inverter within your pump group (Pls. consider reserved
addresses for the MASTER Inverters).


Example:

Multi-pump-system with 3 MASTER and 4 BASIC Inverters

• Set address 1-3 for the MASTER Inverters via appropriate software parameters

(See submenu CONF INVERTER [0200] or submenu RS485-INTERFACE [1200])

• Address 4-7 for the BASIC Inverters via dip-switch


The pre-selected address is also responsible for the pump sequence.









Setting of the correct address:

o

The HYDROVAR must be disconnected from power supply at least for 5 minutes
before removing the top-cover
(open four fastening screws)!

o

Use the dip-switch which is on the power unit (see picture next page!)

o

Set the desired address for each HYDROVAR
E.g. Address 4 ->

switch 1 is set to OFF
switch 2 and 3 are set to ON

o

Mount the cover on the HYDROVAR and tighten the four fastening screws

o

Reconnect HYDROVAR to power supply


Switch

1

Switch

2

Switch

3

Address

OFF OFF OFF

Address 1 (default setting)

(Required setting for the use with control card)

OFF OFF ON

Address

2

OFF ON OFF

Address

3

OFF ON ON

Address

4

ON OFF OFF

Address

5

ON OFF ON

Address

6

ON ON OFF

Address

7

ON ON ON

Address

8

switch 4 not used!