Example for using the Offset function:

Constant pressure system with required value of 5 bar.
Additionally a flow sensor is connected to the Offset input.

Parameter [907] - Offset Range = 160 (max. range of flow sensor = 16m³/h)

System requirement 1:
5 bar constant pressure while the flow rate is between 5m³/h and 12m³/h.
Below the 5 m³/h the pressure should be decreased with the limitation to have max. 2,5 bar

at a flow rate of 2m³/h.

Settings:
Parameter [0910] - Level 1 = 50 = 5m³/h (first limit where the offset function is active)

Parameter [0912] - Offset X1 = 20 = 2m³/h (fixed point according the requirements)
Parameter [0913] - Offset Y1 = 2,5 = 2,5bar (max. allowed pressure at this flow rate)

System requirement 2:
5 bar constant pressure while the flow rate is between 5m³/h and 12m³/h.

Above the 12 m³/h the pressure should be increased with the limitation to have max. 6,0
bar at max. flow rate of 16m³/h.

Settings:

Parameter [915] - Level 2 = 120 = 12m³/h (second limit where the offset function is active)
Parameter [917] - Offset X2 = 160 = 16m³/h (fixed point according the requirements)

Parameter [918] - Offset Y2 = 6 = 6bar (required pressure at this flow rate)