Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 75

Advertising
background image


75

Possible settings:

- analog I 4-20mA

- analog I 0-20mA

- analog U 0-10V

For correct operation the suitable signal input type regarding to the connected sensor has
to be selected.

Sensor type:

Terminals:

- analog I 4-20mA
- analog I 0-20mA

The actual value is represented by a current
signal connected to following terminals:

X3/2 -> Sensor 1

* X3/4 -> Sensor 2

- analog U 0-10V

The actual value is given from a voltage signal
connected to following terminals:

X3/6 -> Sensor 1

* X3/5 -> Sensor 2

* … Sensor 2 is not available for the SINGLE Inverter configuration

0420

0420 SENS. RANGE

20mA = 10.00 Bar

Sensor range

Possible settings:

0.00 – 10000

Determines the end value (=20mA or 10V) of the connected sensor.
The maximum sensor range -> 20mA = 100% of the sensor range must be set.

For example:
10 bar pressure sensor

=> 20mA = 10bar

0.4 bar differential pressure sensor

=> 20mA = 0.4 bar

Flowmeter (Flowrate= 36m³/h)

=> 20mA = 36m³/h

0425

0425 SENS. CURVE

linear

Sensor curve

Possible settings:

linear, quadratic


Internal calculation based on the actual value
Possible setting and its application:

linear:

Pressure control, differential pressure control, level, temperature and
flow control (inductive or mechanical).

quadratic: Flow control using an orifice plate together with a differential pressure

sensor.


0415

0415 SENSOR TYPE

4 – 20mA

Selection of the sensor type and input terminal