Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 91

Advertising
background image


91

1200

1200 SUBMENU RS485-

INTERFACE


User Interface
The following 3 Parameters are necessary for the communication between the HYDROVAR
and an external device (e.g. PLC) via standardized Modbus-protocol. Set desired address,
Baudrate and Format according the system requirements.

1205

1205 ADDRESS

1

Set desired address for the user interface

Possible settings:

1 - 247

1210

1210 BAUDRATE

9600

Baudrate for user interface

Possible settings:

1200, 2400, 4800, 9600, 14400, 19200, 38400

1215

1215 FORMAT

RTU N81

Format for user interface

Possible settings:

RTU N81, RTU N82, RTU E81, RTU O81,

ASCII N72, ASCII E71, ASCII O71


Internal Interface
If several MASTER Inverters are connected via the internal RS-485 interface (max. 8 / using
cascade serial mode) each HYDROVAR needs its own allocated pump-address number (1-8).
Each address may only be used once!

1220

1220 PUMP ADDR.

1

Select desired address for the MASTER Inverter

Possible settings:

1-8

Set desired address for the current MASTER Inverter and press

button for approx. 3 sec.

and the following massages will appear:

Addressing
Addressing

->

1220 PUMP ADDR.

* 1 *

or

1220 PUMP ADDR.

- 1 -

Addressing done

Addressing failed - retry

When using MASTER and BASIC Inverters together in a multi-pump-system you have to
consider that the BASIC Inverters have their separate address. Otherwise a correct function
of the system couldn’t be guaranteed.
For detailed Information see chapter 9.4.3.2 Addressing.