RA: Ramp F

min

acceleration

Actual Value

RD: Ramp F

min

deceleration Output

Frequency

R1: Ramp 1 – speed ramp fast increase
R2: Ramp 2 – speed ramp fast decrease
R3: Ramp 3 – speed ramp slow increase
R4: Ramp 4 – speed ramp slow decrease

Ramp settings:

• Time settings of the ramps influence the control of the pump.
• The fast ramps 1 and 2 are determined by the type (power) of the HYDROVAR and the

type of the pump.

Default = 4 sec.; depending on the power of the HYDROVAR they should be increased
up to 15s for higher power ratings to avoid overload error.

,

• The slow ramps 3 and 4 determine the regulation speed of the internal HYDROVAR

controller for small devices or constant consumption and depend on the system, which
has to be controlled. (Default = 70 sec.)


• The Ramps FminA and FminD are used for a start-up and shut off. These parameters

allow fast acceleration and deceleration and especially should be used for applications

where pumps or other devices are powered, which shouldn’t work below a determined
frequency for a certain time. (to prevent damages or decrease abrasion)


To adjust the Ramps, press

or

Set HYSTERESIS [0315] in %

set rated REQUIRED VALUE [02]

WINDOW [0310]

setting in % of

the required

MIN FREQ [0250]

t [s]

Set HYSTERESIS [0315] in %

FMIN TIME [0260]