0600 0600 SUBMENU ERRORS

0605

0605 MIN. THRESH.

disabled

minimum threshold limit

Possible settings:

disabled - max. SENSOR RANGE


• An adjusted value >0.00 has to be reached within the programmed DELAY TIME [0610]
• If this value can’t be reached, the HYDROVAR stops with the failure message MIN.

THRESHOLD ERROR.

• To disable the minimum threshold limit, press

till disabled is shown on the display.

0610

0610 DELAY - TIME

2 Sec

minimum threshold limit delay time

Possible settings:

1 – 100 sec

Delay time to switch-off the HYDROVAR in case the actual value drops below the min.
threshold limit or a connected external low water protection at terminals X3/11-12 has
been opened.
Notice: The min. threshold function is also active during start up of the pump!
Therefore the delay time has to be set higher than the duration that is needed, to reach a
value above the limit.

0615

0615 ERROR RESET

ON

Automatic error reset

Possible settings:

ON – OFF

ON: Allows an automatic restart for 5 times in case of a failure. If the failure is still active

after the 5

th

restart, the HYDROVAR will shut off and the appropriate error message is

shown.

The internal counter of the automatic error reset is decreased by 1 after each operating

hour, so if an error could be reset after 3 restarts, there are 3 further restarts possible after
one hour, 4 after two hours and 5 automatic restarts after 3 operating hours.
A manual reset can be done by switching an external ON/OFF (X3/7-8) contactor.

Not each error can be reset automatically.
(For detailed information see chapter 11 failure messages)

OFF: if the ERROR RESET is set to OFF, each failure would be shown on the display directly
and must be reset manually.