Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 84

Advertising
background image


84

0805

0805 C.REQ.VAL 1

digital

Configuration required value 1

Possible settings:

- digital

- analog U 0-10V

- analog I 0-20mA

- analog I 4-20mA

Digital

The internal required value 1 is used.
Setting in the main menu in Parameter 02 or parameter

[0820].

analog U=0 – 10V

The required value 1 is determined by the value of a voltage signal
(0 – 10V) connected to terminals X3/13- X3/14 (GND).

analog I=0 – 20mA

analog I=4 – 20mA

The required value 1 is determined by the value of a current signal
(4 – 20mA or 0 – 20mA) connected to terminals X3/18- X3/17
(GND).
Notice: If the incoming current signal drops below 4mA (4-20mA
setting), a warning message is shown on the display. If the failure is
still active after 20 seconds, an error message will be shown.


The changeover between the 1

st

and the 2

nd

required value can be done either internally or

externally via the digital inputs. With the following parameters the source of the required
values and the change over can be configured.

0810

0810 C.REQ.VAL 2

OFF

Configuration required value 2

Possible settings:

- OFF

- digital

- analog U 0-10V

- analog I 0-20mA

- analog I 4-20mA

OFF

Required value 2 is not used.

digital

The internal required value 2 is used.
Setting in the main menu in Parameter 02 or Parameter

[0825].

analog U 0 – 10V

The required value 2 is determined by the value of a voltage
signal (0 – 10V) connected to terminals X3/15- X3/16 (GND).

analog I 0 – 20mA

analog I 4 – 20mA

The required value 2 is determined by the value of a current
signal (4 – 20mA or 0 – 20mA) connected to terminals
X3/23- X3/22 (GND).
Notice: If the incoming current signal falls below 4mA (4-20mA
setting), a warning message is shown on the display. If the failure is
still active after 20 seconds, an error message will be shown.


0800

0800 SUBMENU

REQUIRED VALUES

S

S

S