Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 72

Advertising
background image


72

0300

0300 SUBMENU

REGULATION

0305

0305 JOG 0.0Hz

X.XX Bar

Both the current output frequency and actual value

are shown.

• By pressing

or

in this menu, the internal controller of the HYDROVAR is

deactivated and it changes to manual mode.

• Using the

and

buttons any constant speed can be set without further control to

achieve the set point!

• If this value becomes 0.00 Hz the HYDROVAR stops.
• As soon as the window is

left by pressing

or

►,

the HYDROVAR returns to the

selected mode.

0310

0310 WINDOW

5%

range of ramp control

Possible settings:

0 – 100% of required value

• Determines the band, where the slow ramp changes to the fast ramp
• for steep pump-curves and closed loop systems ~20-30%

0315

0315 HYSTERESIS

80%

Hysteresis for ramp switching

Possible settings:

0 – 100%

• Determines the band, where the normal regulation is done

(change between the slow ramps)

• for an accurate control (without automatic shut-off) ~99%, e.g. constant flow control

0320

0320 REG. MODE

normal

Regulation mode

Possible settings:

normal, inverse

Normal: Speed is increased with falling actual value signals. (e.g.: control at constant
output pressure)

Inverse: Speed is reduced with falling actual value signal. (e.g.: control at constant suction
pressure or at constant level on the suction side)