Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 54

Advertising
background image


54

04

04 START VALUE

OFF


Regulation Restart Value

Possible settings:

0 – 99 % – OFF

This parameter defines the start value after pump stop in percentage of the required value.

E.g. REQUIRED VALUE [02]: 5.0 bar

START VALUE [04]: 80 % --> 4.0 bar

If the pump system has reached the required pressure of 5.0 bar and there is no more
consumption, the HYDROVAR shuts off the pump.
When the consumption increases, and the pressure drops the pump normally starts. If a
START VALUE [04] of 4.0 bar has been selected the pump won’t start until the pressure

drops below.

The following parameters in the main-menu are valid for all selected modes:

05

05 LANGUAGE

ENGLISH

Language selection

Possible settings:

To select the desired language press ▲ or ▼


The information on the display and all parameters are available in various languages. The
languages available are split in different language blocks which support different language
sets.

For detailed information see chapter 4.

With the following two parameters the current date and time, can be set. This is used to
display failure messages with accurate date and time when the failure occurred.

06

06 DATE

DD.MM.YYYY

Current date

Set the date by pressing

for approx. 3 sec.

to set current DAY / MONTH / and YEAR.

07

07 TIME

HH:MM

Current time

Set the time by pressing

for approx. 3 sec.


to set current HOUR and MINUTE.


S

S

G