32

To ensure safety

operation between the HYDROVAR and the motor a motor-thermo-switch

or PTC should be connected to the power unit. Additionally this input can be used as an

external ON / OFF signal when using the HYDROVAR just as BASIC Inverter. Both the signals
must be connected to X1/PTC in series and will stop the HYDROVAR in case of a failure!

(Also a low-water switch or any other protective devices can be connected to these
terminals!)
If there is no use of this input, terminals X1/PTC have to be bridged, otherwise the
HYDROVAR will not start automatically.

9.4.3.1 Solo run
The terminals X1/SL are used to release a BASIC Inverter (when used in a multi-pump
application) when the communication to the MASTER Inverter fails, or even the MASTER

Inverter fails itself, or in case the BASIC Inverter is just used as a

simple soft-starter.

• By opened

contact X1/SL the HYDROVAR works in standard operation. So a BASIC

Inverter only starts up, if it is released and requested by a MASTER Inverter via the serial
RS485-Interface.

• When contact X1/SL is closed the HYDROVAR starts up to pre-selected MAX. FREQUENCY

(fixed speed) [0245] using Ramp 1 and 2 and even the fast ramps FminA and FminD.
(X1/PTC must be closed too - all external connected safety devices are still active)

A manual start up is always possible, even the HYDROVAR is equipped with a control card.
For example, if it is necessary because of safety reasons to operate the BASIC Inverters
when the MASTER Inverters fail, it is possible to equip this terminal with an AUTO/MANUAL
switch.

Connection Example

External switch to enable the
SOLO RUN


for example:
External release or
Low water switch

PTC or thermo-switch
(mounted in the motor terminal box)

Recommended connections of external protective devices:
BASIC Inverter:

PTC or thermal switch

X1/PTC

External

release

X1/PTC

Low

water

switch

X1/PTC

Placed on the power unit


MASTER Inverter:

PTC or thermal switch

X1/PTC

Placed on the power unit

External

release

X3/7-8

Low

water

switch

X3/11-12

Placed on the control card