Control terminals
All control cables connected to the control card have to be screened (See chapter 9.3

recommended cable types).
External volt free contacts must be suitable for switching <10 VDC.

NOTE: If unscreened control cables are used, signal interference may occur
and could also interfere incoming signals and the function of the
HYDROVAR.

Do not connect the ground of the control card to other voltage potentials.
All electronic ground terminals and GND of the RS 485-interface are connected internally.

X3 Digital and Analogue I/O

1 GND, electronic ground

2 Actual value current input sensor 1

0-20mA / 4-20mA [Ri=50Ω]

3 Power supply for external sensors

24VDC, ** max. 100mA

4 Actual value current input sensor 2

0-20mA / 4-20mA [Ri=50Ω]

5 Actual value voltage input sensor 2

*Dig 3 0-10 VDC

6 Actual value voltage input sensor 1

*Dig 2 0-10 VDC

7 External ON/OFF (release)

Active

low

8 GND, electronic ground

9 Configurable digital input 1

Dig 1

Active low

10 GND, electronic ground

11 Low water

Active

low

12 GND, electronic ground

13 Voltage signal input (required value 1) (Offset) 0-10VDC
14 GND, electronic ground

15 Voltage signal input (required value 2) *Dig 4

(Offset) 0-10VDC

16 GND, electronic ground

17 GND, electronic ground

18 Current signal input (required value 1) (Offset) 0-20mA / 4-20mA [Ri=50Ω]
19
+10V internal ref. for analogue output 10,00VDC,

max.

3mA

20 Analogue output 1

0-10VDC, max. 2mA

21 Analogue output 2

4-20mA

22 GND, electronic ground

23 Current signal input (required value 2) (Offset) 0-20mA / 4-20mA [Ri=50Ω]

X3/

24 +24V power supply for control inputs

24VDC, ** max. 100mA

*

Terminals 5 and 6 can be used as actual value voltage input and also as digital input.

Also the voltage signal input on terminal X3/15 can be used as digital input.

**

X3/3 and X3/24 Æ ∑ max. 100mA

(Offset)

These terminals can be used as required value or offset signal input.

Configuration: see submenu REQUIRED VALUES [0800] and submenu OFFSET [0900].