Motor cables
To ensure the EMC compatibility and minimize noise level and leakage currents, keep the

motor cable as short as possible (use shielded cables only if the total length exceeds 1.5
meters).

Additional component line choke (coil)

Line coils are available as an option and should be mounted between the HYDROVAR and
the main fuse. The Line coil should be as near as possible to the HYDROVAR (max. 30cm).

Advantages:

• better efficiency
• reduction of harmonic currents

For the following applications additional line chokes are strongly recommended:

• high short circuit currents
• compensation-plants without a coil

• asynchronous motors which are responsible for a voltage drop >20% of the line

voltage

EMC summary


• Install potential equalization according to local regulations
• Do not install the power-cables in parallel to signal-cables
• Use screened signal-cables
• Connect both ends of the screen of the motor cable to ground
• Connect only one end of the screen of a signal-cable to ground
• Motor-cable as short as possible
• Pigtails should be prevented


9.3

Recommended Cable Types

To ensure the above mentioned points

and

to guarantee EMC compatibility and correct

function of the HYDROVAR the recommended cable types should be used.

Application Recommended

cable-type

- Motor-cables HV 2.015-2.022

HV 4.022 – 4.030- 4.040

HV 4.055-4.075
HV 4.110
HV 4.150 – 4.185
HV 4.220

4G1,5 + (2 x 0.75)
4G1,5 + (2 x 0,75)
4G2,5 + (2 x 0,75)
4G 4 + (2 x 0,75)
4G6 + (2 x 0,75)
4G10 + (2 x 0,75)

- Control- and signal- cables

JE-Y(ST)Y … BD
JE-LiYCY … BD

- Cables connected to RS485 interface

JE-Y(ST)Y 2 x 2 x 0,8 BD