Reset:

• cutting off the power supply for >60 seconds
• manual reset by closing external ON/OFF (Terminals X3/7-8)
• manual reset by pressing

and

simultaneously for about 5

seconds

• Auto-reset possible if ERROR-RESET [0615] is set to ON

LACK OF WATER

ERROR 21

Low water contact
(X3/11-12) is opened

(just active if motor is running)

• incoming pressure or min. level too

low

• bridge X3/11-12, if there is no ext.

low water protection

• adjust Parameter DELAY TIME

[0610] if the failure happens only
for short time

Reset:

• Automatically if low water contact (X3/11-12) will be closed!

MIN. THRESHOLD

ERROR 22

defined value of parameter
MIN.THRESHOLD [0605] was
not reached during the pre-
selected DELAY-TIME [0610]

• check booster unit, adjust

parameter DELAY TIME [0610]

• Parameter ERROR RESET [0615] set

to ON, to enable 5 restarts

(e.g. in empty system)

FAILURE SENSOR 1

ACT. VAL. SENSOR 1

ERROR 23

Sensor signal on
terminals X3/2 <4mA
active Sensor:

WARNING (20 sec.)-> ERROR
non-active sensor: WARNING

• ACTUAL VALUE signal (pressure

transducer) faulty

• wrong connection
• Sensor or cable fault
• check configuration of the sensors

in submenu SENSORS [0400]

FAILURE SENSOR 2

ACT. VAL. SENSOR 2

ERROR 24

Sensor signal
on terminals X3/4 <4mA

active Sensor:

WARNING (20 sec.)-> ERROR
non-active Sensor: WARNING

• ACTUAL VALUE signal (pressure

transducer) faulty

• wrong connection
• Sensor or cable fault
• check configuration of the sensors

in submenu SENSORS [0400]

SETPOINT 1 I<4mA

SETPOINT 1 I<4mA

ERROR 25

Current signal input of required
values is active, but no signal
4-20mA is connected
WARNING (20 sec.)-> ERROR

• check external analogue signal on

terminals X3/17-18

• check configuration of the required

values in Submenu REQUIRED
VALUES [0800]

SETPOINT 2 I<4mA

SETPOINT 2 I<4mA

ERROR 26

Current signal input of required
values is active, but no signal
4-20mA is connected
WARNING (20 sec.)-> ERROR

• check external analogue signal on

terminals X3/22-23

• check configuration of the required

values in Submenu REQUIRED
VALUES [0800]