Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 78

Advertising
background image


78

The following 3 parameters are responsible for starting the assist pumps and to calculate
the new required value as well.

0505

0505 ACT.VAL.INC.

0.35 Bar

Lift value

Possible settings:

0.00 – to the pre selected sensor range

0510

0510 ACT.VAL.DEC.

0.15 BAR


Drop value

Possible settings:

0.00– to the pre selected sensor range

0515

0515 ENABLE FRQ

48.0 Hz


enable frequency for the next power unit

Possible settings:

0.0 – 70.0 Hz

Using this parameter the desired release frequency for the following pumps can be
selected. If a pump in the system reaches this frequency and the system pressure drops
below the REQUIRED VALUE [02] - ACTUAL VALUE DECREASE [0510], the next pump is
started.

0520

0520 ENABLE DLY

5 sec

Enable delay time (for cascade relay only!)

Possible settings:

0 – 100 sec

If the conditions for starting an assist pump are fulfilled, the fix speed pump will start after
this selected time.

0525

0525 SW DELAY

5 sec

Switch delay (for cascade relay only!)

Possible settings:

0 – 100 sec

Delay time between two switching actions of the fix speed pump.
That parameter prevents the system against repeated switching actions caused by the
variation of the consumption.

0530

0530 DISABLE FRQ

30 Hz

Disable frequency (for cascade relay only!)

Possible settings:

0.0 – 120.0 Hz

The frequency to switch off the fixed speed pumps in cascade relay- mode can be set by
this parameter.