Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 81

Advertising
background image


81

0570

0570 MSTPRIORITY

ON

MASTER priority
(for cascade serial / synchron only!)

Possible settings:

ON - OFF

This parameter determines the alternation order when MASTER and BASIC Inverters are
used within one system. In such a case you have to select if either the MASTER or the BASIC

Inverters should be switched on first.

ON- all MASTER Inverters in the system are released (unless it is stopped by a failure or

manually) before the first BASIC Inverter gets released.

For example:

Address 1-3.......MASTER Inverters

Address

4-8……BASIC

Inverters

Switching order:

Adr 1

MASTER

Adr 2

MASTER

Adr 3

MASTER

Adr 4

BASIC

Adr 5

BASIC

Adr 6

BASIC

Adr 7

BASIC

Adr 8

BASIC

OFF- One MASTER (which is responsible for the controlling according the set value) is

running. With rising consumption all BASIC Inverters have to be released before any
other MASTER starts running.

Switching order:

Adr 1

MASTER

Adr 4

BASIC

Adr 5

BASIC

Adr 6

BASIC

Adr 7

BASIC

Adr 8

BASIC

Adr 2

MASTER

Adr 3

MASTER
























S

G

Advertising