EMC-electromagnetic compatibility

To ensure the electromagnetic compatibility the following points must be observed for

cable installation:

Earth / ground to ensure EMC

Protection earth

It is important to connect the HYDROVAR to PE, because of the earth leakage

current.

HF earth connection

Ground cables should be as short as possible and with lowest impedance.


Signal cables

Control and signal cables should be screened types to prevent disturbances from outside.

The screen should be only connected to ground on one end; to prevent ground loops. The
screen should be connected to HYDROVAR GND (use pre mounted cable-clips).
For small cable diameters the cable clips can be squeezed to ensure fixing.



To connect a screen with lowest impedance to ground, remove the insulation from the
signal cable and connect the screen to ground.


Signal cables must be installed separate from motor- and power- supply cables
If signal cables are installed in parallel to power supply cables (motor cables) for a longer
distance, the distance between these cables should be more than 200mm.
Do not

cross power cables and control cables - if this is not possible, cross them only in an

angle of 90°.