Examples:

Booster unit

Problem: no stop of the HYDROVAR

Parts to check

measure

• existing demand
• non return valve is not closed
• pre charge pressure in the pressure tank


• incorrect setting

of WINDOW and

RAMPHYSTERESIS

• shut down ramp too slow

• suction line too long

• check pipes and valves
• change non return valve
• adjust according the diagram
• set WINDOW [0310] (ca.10%) and

HYSTERESIS [0315] (80-50%)

• set RAMP 2 [0220] to 4...13 sec.

• the MINIMUM FREQUENCY [0250] should be

activated for pressure increase at 0 demand

Control on constant flow

Problem: control fluctuations

Parts to check

measure

control characteristics are set too low

enlarge

r

WINDOW [0310] and set

HYSTERESIS [0315] to 99% to control with
RAMP 3 and 4

Circulating pump

Problem: oscillation of the motor speed

Parts to check

measure

control settings too fast

• increase RAMP 3 [0225] and 4 [0230]:

100...200sec

• WINDOW [0310] (ca.20%) and

HYSTERESIS [0315] (ca.99%)

Problem: ACTUAL VALUE can't be hold

Parts to check

measure

HYSTERESIS is set too big

HYSTERESIS [0315]: 90-99%

General

Problem: pressure fluctuations, analogue signal not constant
Solution: • check cables and connection of the screen

• check earth connection of the transmitter cable

• use screened cables