Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 69

Advertising
background image


69

f->f

min

With this setting the pump will never stop automatically. Only the frequency will go

down to the selected MINIMUM FREQUENCY [0250]. To stop the pump the external
ON/OFF must be opened or the

button must be pressed.

0260

0260 FMIN TIME

0 s


Delay time before shut off below MIN. FREQ.

Possible settings:

0 – 100 sec

After running the pump for this selected time at minimum frequency, the pump will stop, if
parameter

CONFIG. FMIN [0255] is set to f -> 0



0265

0265 BOOST

5 %

Setting of the motor starting voltage in % of
connected supply voltage

Possible settings:

0 – 25% of the input voltage

This parameter determines the characteristics of the voltage/frequency curve.
In particular, it refers to the voltage increase during the motor starting stage as a
percentage of the nominal voltage. Take care that settings are kept as low as possible so
that the motor does not become thermally overloaded at lower frequencies.
If the boost is set too low, a failure (OVERLOAD) may occur because the starting-current is
too high.

0270

0270 KNEE FRQ.

50.0 Hz

Knee frequency

Possible settings:

30.0 – 90.0 Hz

With this parameter you can set the frequency, at which the HYDROVAR should generate
its maximum output voltage (=value of connected input voltage).
For standard applications this frequency should be set according the MAX. FRQ. [0245]
(Default Setting 50Hz).

Be careful: This parameter should be used for special applications only!
Incorrect setting can cause an overload error and even a damage of the
motor.


Applications: circulation systems

The setting f->f

min

can overheat the pump, when there is no flow through

the pump => bypass line for circulation pumps!

NOTE:

Problems with shut off the pump at no demand (too small or no pressure
tank) may be solved as the system pressure is increasing during this delay-

time.