b) Active MODE [0105] = Cascade Relay / Cascade Serial / Cascade Synchron

* ADR X PX XX.X Hz

STOP X.XX Bar

1

st

display at mode cascade serial and cascade relay


This window shows the status of the HYDROVAR.
*

Indicates the HYDROVAR which actually controls the system

ADR X Pump address

P X

Cascade relay mode: Indicates the number of pumps which are running

e.g.: P3 …. MASTER + 2 fixed speed pumps are running

Cascade serial/synchron mode: Indicates the sequence of the pumps in the
system, depending on the MASTER PRIORITY [0570] and SWITCH INTERVAL [0555]

ON Automatic

and external released

Stop of the HYDROVAR by pressing

STOP Manually

stopped

Start of the HYDROVAR by pressing

OFF

External release (X3/7-8) is open

To start up the HYDROVAR close external
release or bridge terminal X3/7-8


Indication for MODE – Controller / Cascade Relay / Cascade Serial / Cascade Synchron

02

02 REQUIRED VAL

D1 X.XX Bar

Set the desired required value with

or


The current REQUIRED VALUE and its source (by the additional information) are shown in
this window.

D1 internal - required value 1 (set by parameter 0820)
D2 internal - required value 2 (set by parameter 0825)
U1 required value 1 - voltage signal input (Connected to X3/13)
U2 required value 2 - voltage signal input (Connected to X3/15)
I1

required value 1 – current signal input (Connected to X3/18)

I2

required value 2 – current signal input (Connected to X3/23)








S

G