Mode CASCADE RELAY:

Device enabled

by

1 MASTER

Inverter

2

fixed speed pump

Relay 1 X10 /1

3

fixed speed pump

Relay 2 X10 /2

4

fixed speed pump

Relay 3 X10 /3

5

fixed speed pump

Relay 4 X10 /4

6

fixed speed pump

Relay 5 X10 /5

7 not

used

8 not

used

23

23 STATUS DEVICE

Stopped


Status of the selected device

Possible messages: Running, Stopped, Disabled, OFF, Preparing (Mode Casc. Serial/Synchr)
relay on, relay off

(Mode: Cascade Relay)

Solorun, Faulted (all Modes)
Shows the status of the device
Mode CASCADE RELAY:
relay_on

->

Relay contact is closed -> fixed-speed-pump is running

relay_off

->

Relay contact is opened -> fixed-speed-pump is stopped

Mode CASCADE SERIAL/SYNCHRON:
running

->

Pump is running

stopped

->

Pump is stopped, because there is no request

disabled

->

Pump is stopped manually
(Stopped with buttons or disabled with parameter ENABLE DEVICE [24])
or by external device (external on/off contact open)

OFF

->

Pump is not connected to power supply

Pump is not connected via RS485 interface

preparing

->

A new unit is connected to the multi-pump system and

Data

is

transferred

solo run

->

Solorun is activated (X1/SL closed)

faulted

->

A failure occurred on the current unit

24

24 ENABLE DEVICE

Enable


Enable – Disable of the selected device

Possible settings:

Enable - Disable

The selected device can be enabled or disabled manually.
(Either in cascade relay / serial / synchron or controller mode).