Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 85

Advertising
background image


85

0815

0815 SW REQ. VAL

Setpoint 1


Switching between required value 1 and 2

Possible settings:

- Setpoint 1

- Setpoint 2

- Switch Dig 1

- Switch Dig 2

- Switch Dig 3

- Switch Dig 4

Setpoint 1:

Only required value 1 is active (No switching possible)

Setpoint 2:

Only required value 2 is active (No switching possible)

Switch Dig 1:

Manual switching by closing digital input 1 (X3/9-10)

Switch Dig 2:

Manual switching by closing digital input 2 (X3/6-10)

Switch Dig 3:

Manual switching by closing digital input 3 (X3/5-10)

Switch Dig 4:

Manual switching by closing digital input 4 (X3/15-16)

0820

0820 REQ.VAL.1

XX.X Bar

Required value 1 (digital)

Possible settings:

0.0 – to the pre selected sensor range

0825

0825 REQ.VAL.2

XX.X Bar

Required value 2 (digital)

Possible settings:

0.0 – to the pre selected sensor range

Set the desired required value with either

or

▼.

This pre-selected required value is active in all modes except Actuator if parameter
C.REQ.VAL.1 [0805] or C.REQ.VAL.2 [0810] is set to digital, and parameter SW REQ.VAL.
[0815] is set to setpoint 1/2 or the REQUIRED VALUE 1/2 is selected via digital input.
This pre-selected required value could also be taken over in the main menu with parameter
REQUIRED VAL. [02] if the current required value is active.

0830

0830 ACTUAT.FRQ 1

XX.X Hz

Required frequency 1 for actuator

Possible settings:

0.0 – MAX. FREQ. [0245]

0835

0835 ACTUAT.FRQ 2

XX.X Hz

Required frequency 2 for actuator

Possible settings:

0.0 – MAX. FREQ. [0245]

Set the frequency with either

or

The selected frequency in this parameter is only active in the actuator mode if parameter
C.REQ.VAL.1 [0805] or C.REQ.VAL.2 [0810] is set to digital, and parameter SW REQ.VAL
[0815] is set to setpoint 1/2 or the ACTUATOR FREQUENCY 1/2 is selected via digital input.