Xylem HYDROVAR HV 4.150 / 4.185 / 4.220 User Manual

Page 48

Advertising
background image


48

X5 Status-Relays

1

CC

2

NC

3

Status Relay 1

NO

4

CC

5

NC

X5/

6

Status Relay 2

NO

[Max. 250VAC]
[Max. 220VDC]

[Max. 30VDC]

[0,25A]
[0,25A]

[2A]

Status Relay 1

Status Relay 2

Notice:
When using the relay contacts for
driving an external relay, a
corresponding RC-snubber-circuit or
varistor is

recommended, to prevent

disturbances arising during a switching
action of the relay!


Both Status-Relays on the control card can be used regarding the programmed
configuration.


Factory setting: The two relays are used as pump-running or fault-signal-relay.
For this application see connection example below (How to program see parameters
CONF REL 1 [0715] and CONF REL 2 [0720]).
Connection examples:

Pump running signal

Fault signal

X5/ 1 and 3 closed:
- motor run indication

X5/ 4 and 5 closed:
- if there is a fault/error

Ext. 250VAC / 220VDC

Ext. 250VAC / 220VDC